[:en]Description of the floating neutral phenomenon when some inverters go into autonomous mode.
**** Beware, electricity is dangerous because it is invisible, silent and odorless.
The consequences can be fatal if you do not master this subject ****
The neutral is no longer grounded, so it is in floating mode. 110V on the blue and 120V on the phase.
This would not be a problem if it did not put your electrical box out of play and especially the differentials that can no longer detect a leakage current and therefore break.
I do not understand how these inverters can be sold in France ?
Explanatory video below
[yotuwp type= »videos » id= »z6DRaXrBN1M » ][:fr]Description du phénomène du neutre flottant lorsque certains onduleurs se mettent en mode autonome.
**** Attention l’électricité est dangereuse car invisible, silencieuse et inodore.
Les conséquences peuvent être fatales si vous ne maîtrisez pas ce sujet ****
Le neutre n’est plus mis à la terre, donc il se retrouve en mode flottant. 110V sur le bleu et 120V sur la phase.
Ceci ne serait pas gênant si cela ne mettait pas hors jeux votre coffret électrique et surtout les différentiels qui ne peuvent plus détecter un courant de fuite et donc disjoncter.
Je ne comprends pas comment ces onduleurs puissent être vendus sur France ?
Vidéo explicative ci-dessous
[yotuwp type= »videos » id= »z6DRaXrBN1M » ][:]
salut, j’ai eu le meme problème et je l’ai résolu en shuntant la sortie AC neutre et la terre, avec une résistance de 1KOHM a 0.01€, cordialement
Ça je n’aurais pas osé. Mais si ça fonctionne, il n’y a pas de raison de ne pas le partager. En effet, solution à 0€, radicale.
On ne voit pas trop bien la résistance et ses connexions. Pourrais-tu en poster une plus grande et bonne définition ?
Question, as-tu mis un testeur de phases pour vérification ainsi que de tester un courant de fuite pour voir si ton tableau électrique détecte bien la fuite de courant ?
Ce serait cool.